Function
Product Specifications
Specifications

CPU
CPU frequency 528MHz, RAM 512MB, ROM 4GB

Signal Input/Output
Serial 1 and Serial 2 are RS232 and RS485 multiplexing excuses, Serial 3,
Serial 4 and Serial 5 are RS485 interfaces

Communication Ports
MODBUS RTU master with 5 RS485 serial ports

External Communication Interface
8 points, Input range 4~20mA, 16-bit resolution with diagnostics

External Interface
2 10/100Mbps Ethernet ports (supports redundant configurations), 5 serial ports (2 RS232/RS485 switchable serial ports, 3 RS485 serial ports) at rates up to 115.2Kbps

Communication Gap
Communication distance up to 500m at baud rate 9600bps

Expansion Equipment
Expand the number of third-party devices that the control system can access
structure
Product Features


- With rail and wall-mounted placement requirements, suitable for various types of cabinets
- Dual network port redundancy, more stable equipment operation
- Wide-temperature operation, shockproof, dustproof and drop-proof
- Web configuration, data monitoring, query, import/export, easy and convenient
- Complete set of ports with high-level protection measures
- Powerful data transmission capability, can be directly merged into the cloud
- Built-in serial gateway, supports MODBUS TCP and MODBUS RTU inter-conversion
- RS485 serial port extends devices by bus mode, up to 30 devices
structure
System Structure
The serial server function of EN2000 realizes the data passthrough mode.
EN2000, as a transparent device, no longer initiates MODBUS requests
independently, but passthroughs the requests from the upper MODBUS master to the
lower MODBUS slaves, and passthroughs the answer data from the slaves to the
upper MODBUS master. In the passthrough mode, the upper MODBUS master has to
manage all the slaves below it by itself.?